Data sheet
1Description
The UT 6-TMC M circuit breaker is a single-position
overload circuit breaker with thermomagnetic tripping. It is a
space-saving circuit breaker with trip-free mechanism in the
event of overload and short circuits within the maximum
interrupting rating. The UT 6-TMC M is mounted on an
NS 35 DIN rail.
UT 6-TMC M thermomagnetic circuit breakers feature a
compact design, large labeling areas, and a double plug-in
bridge shaft.
The circuit breakers provide a high level of system
availability thanks to their reclosure function and clear status
display.
Eleven nominal current versions can be selected from 0.5 A
to 16 A. The large center labeling area enables clear
assignment of the relevant circuit breaker.
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC) (see page 3). The
magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
NOTE: When mounted in rows with simultaneous load, a mutual thermal effect occurs (see page 4).
Calibration is required for an ambient temperature of +23°C. A correction factor must be used to determine the
nominal current for a lower or higher ambient temperature (see page 5).
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
Thermomagnetic circuit breakers
UT 6-TMC M...
103943_en_04 PHOENIX CONTACT 2
2Ordering data
3 Electrical data
Circuit breakers
Description Nominal current Type Order No. Pcs./Pkt.
Thermomagnetic circuit breaker, 1-pos. 0.5 A UT 6-TMC M 0,5A 0916603 6
Thermomagnetic circuit breaker, 1-pos. 1 A UT 6-TMC M 1A 0916604 6
Thermomagnetic circuit breaker, 1-pos. 2 A UT 6-TMC M 2A 0916605 6
Thermomagnetic circuit breaker, 1-pos. 4 A UT 6-TMC M 4A 0916606 6
Thermomagnetic circuit breaker, 1-pos. 5 A UT 6-TMC M 5A 0916607 6
Thermomagnetic circuit breaker, 1-pos. 6 A UT 6-TMC M 6A 0916608 6
Thermomagnetic circuit breaker, 1-pos. 8 A UT 6-TMC M 8A 0916609 6
Thermomagnetic circuit breaker, 1-pos. 10 A UT 6-TMC M 10A 0916610 6
Thermomagnetic circuit breaker, 1-pos. 12 A UT 6-TMC M 12A 0916611 6
Thermomagnetic circuit breaker, 1-pos. 15 A UT 6-TMC M 15A 0916612 6
Thermomagnetic circuit breaker, 1-pos. 16 A UT 6-TMC M 16A 0916613 6
Accessories
Description Type Order No. Pcs./Pkt.
Plug-in bridge, for cross connection in the bridge shaft, red, 2-pos. FBS 2-6 3030336 50
Plug-in bridge, for cross connection in the bridge shaft, red, 3-pos. FBS 3-6 3030242 50
Plug-in bridge, for cross connection in the bridge shaft, red, 4-pos. FBS 4-6 3030255 50
Plug-in bridge, for cross connection in the bridge shaft, red, 5-pos. FBS 5-6 3030349 50
Plug-in bridge, for cross connection in the bridge shaft, red, 10-pos. FBS 10-6 3030271 10
Plug-in bridge, for cross connection in the bridge shaft, red, 20-pos. FBS 20-6 3030365 10
Warning label, for UT series, yellow WS UT 6 3047345 10
Screwdriver SZS 1,0X4,0 1205066 10
UniCard sheet, for labeling UC-TM 12 (See CLIPLINE catalog)
Zack marker strip, for labeling ZB 12 (See CLIPLINE catalog)
Nominal current, nominal voltage, and additional electrical data
Rated insulation voltage 440 V AC
Rated frequency 50/60 Hz (at 240 V AC)
Nominal voltage 240 V AC, 28 V DC
Nominal current AC/DC Depending on module: 0.5 A, 1 A, 2 A, 4 A, 5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 16 A
Operating voltage range 50 V AC ... 264 V AC, 5 V DC ... 30.8 V DC
Operating frequency range 48 Hz ... 62 Hz
Insulation resistance (main circuit) > 100 MΩ
Insulation resistance 50 Hz: 2000 V
Pulse: 2800 V
Surge voltage category II
Pollution degree 2
AC DC
Switching cycles
Service life under load
Overload according to IEC 60943
Overload according to UL 1077
6000 cycles at 1 x In
40 cycles at 6 x In
50 cycles at 1.5 x In
6000 cycles at 1 x In
40 cycles at 6 x In
50 cycles at 1.5 x In
Short-circuit switching capacity (Inc) 200 A 400 A
Conditional short-circuit switching capacity (Inc)[Backup fuse] 2000 A 2000 A
UT 6-TMC M...
103943_en_04 PHOENIX CONTACT 3
3.1 Tripping characteristics
Figure 1 AC and DC tripping characteristics
Backup fuse Nominal current
UT 6-TMC M
Maximum backup fuse
The following maximum backup fuse values are recommended according to
characteristic gG (VDE 0636, IEC 269)
0.5 A 16 A
1 A 16 A
2 A 16 A
4 A 16 A
5 A 20 A
6 A 20 A
8 A 25 A
10 A 25 A
12 A 25 A
15 A 25 A
16 A 25 A
NOTE: If in the application the maximum short-circuit switching capacity (Icn) could be exceeded in the event of an error, a backup fuse
must be used in combination with the circuit breaker.
Tripping characteristics
Type of actuation Manual ON/OFF (S type)
Tripping method Thermomagnetic (TM)
Tripping type Trip-free mechanism
Specified non-tripping current (no tripping within an hour) 1.05 x In
Specified tripping current (tripping within an hour) 1.32 x In
Instantaneous non-tripping current 6 x In (AC)
Instantaneous tripping current 12 x In (AC)
NOTE: The magnetic tripping ranges differ for alternating currents (AC) and direct currents (DC). Please observe the tripping characteristics
shown in Figure 1.
The magnetic operating currents for direct currents (DC) are approximately 1.6 times higher.
Switching time [s]
Switching time [s]
Multiples of IN
Multiples of IN
10000
1000
100
10
1
0.1
0.01
0.001 122034 406608 10 100
< 7.0A
> 7.0A
10000
1000
100
10
1
0.1
0.01
0.001 122034 406608 10 100
< 7.0A
> 7.0A
AC tripping characteristics DC tripping characteristics
UT 6-TMC M...
103943_en_04 PHOENIX CONTACT 4
3.2 Effect on thermal tripping of mounting in rows
The mutual thermal effect is tantamount to an increase in the
ambient temperature (see page 5). This depends on the
following:
The nominal current
The ambient temperature
The number of devices
The distance between devices
The nominal device current can be either overdimensioned
or limited. When the UT 6-TMC M is mounted in rows, the
correction factor is usually in the range of 1.25 or at
80% (reciprocal) in relation to the limiting nominal current.
These values apply in the event of continuous load and at an
ambient temperature of +23°C.
Since the thermal effect varies for each planned installation
when mounting in rows, the correction factors must be
defined individually and tested.
Calculation example for overdimensioning
5 circuit breakers with In = 10 A are to be mounted in rows.
The ambient temperature is +23°C.
3.3 Internal resistance of the UT 6-TMC M
Measurement between the LINE and LOAD connections.
Tolerance: ±10%
4 Mechanical data
NOTE: When mounted in rows with simultaneous
load, a mutual thermal effect occurs.
Nominal current when not mounted
in rows
In = 10 A
Typical correction factor df = 1.25
Theoretical nominal current when
mounting in rows
In row = 10 A X 1.25
= 12.5 A
Nominal current Resistance
0.5 A 4.37 Ω
1.0 A 0.95 Ω
2.0 A 0.33 Ω
4.0 A 88.0 mΩ
5.0 A 55.8 mΩ
6.0 A 41.7 mΩ
8.0 A 22.2 mΩ
10.0 A 12.3 mΩ
12.0 A 10.9 mΩ
15.0 A 8.3 mΩ
16.0 A 7.7 mΩ
Fixing
Mounting method On a DIN rail according to DIN EN 60715, NS 35N/7,5 or NS 35/15
The tripping characteristics are not dependent on the mounting position.
Plug-in bridge, for cross connection in the bridge shaft FBS x-6 plug-in bridge (see "Accessories" on page 2)
Connection polarity Independent polarity (for DC) for the LINE and LOAD connections
Suitability "Factory wiring"
Weight 51 g
Housing material PA 66
Fuse type Medium blow fuse
Inflammability class according to UL 94 V0
Maximum number of cycles 6000 at 1 x In
Connection terminal block
Screw connection M4
Connection capacity Solid Stranded With ferrule
1 conductor 0.2 mm² ... 10 mm² 0.2 mm² ... 10 mm² 0.25 mm² ... 6 mm²
2 conductors (two conductors with same cross-section, ferrule without
plastic sleeve)
0.2 mm² ... 2.5 mm² 0.25 mm² ... 1.5 mm²
2 stranded conductors with a TWIN ferrule 0.5 mm² ... 4 mm²
Stripping length 12 mm
Tightening torque (EN 60934) 1.5 Nm ... 1.8 Nm
2“ an 1.0 227 397 Has \ll‘lfifiiijl El 123
UT 6-TMC M...
103943_en_04 5
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
5 Environmental influences
5.1 Temperature range, influence on the ambient
temperature
The following typical correction factors must be observed to
calculate the nominal current:
Correction factors
Example calculation:
A circuit breaker with In= 4 A is to be used at an ambient
temperature of +60°C.
5.2 IP protection class
5.3 Resistance to vibrations and shocks
5.4 Approvals
6Dimensions
Figure 2 Dimensions (in mm)
NOTE: Calibration is required for an ambient
temperature of +23°C.
Temperature range -30°C … +60°C
Reference temperature +23°C
°C
In [A] -30 -20 -10 0 10 23 30 40 50 60
0.5 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
1 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.06 1.13 1.19
2 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
4 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.21
5 0.77 0.81 0.84 0.87 0.90 1.00 1.03 1.08 1.15 1.25
6 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21
8 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.06 1.13 1.21
10 0.78 0.81 0.84 0.87 0.90 1.00 1.05 1.15 1.21 1.30
12 0.77 0.80 0.85 0.90 0.95 1.00 1.03 1.08 1.15 1.21
15 0.73 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.11 1.21
16 0.70 0.73 0.78 0.84 0.90 1.00 1.03 1.08 1.15 1.21
ø 0.75 0.78 0.82 0.86 0.90 1.00 1.03 1.08 1.15 1.22
Nominal current at +23°C In (+23°C) = 4 A
Ambient temperature Tamb = +60°C
Correction factor df = 1.21
Theoretical nominal current at +60°C
In (+60°C) = 4 A x 1.21 = 4.84 A
At +60°C, a nominal current of 5 A should be selected.
IP protection class Actuation area IP40
Connection area IP20
Shock resistance according to EN 60068-2-27,
Test Ea [3 shocks in each direction (= 18 shocks)]
Peak G Pulse length Pulse form
50g 11 ms Half-sine
Vibration resistance according to EN 60068-2-6,
Test Fc - frequency range: 5 Hz ... 500 Hz
< 60 Hz
(constant amplitude)
> 60 Hz
(constant acceleration)
0.15 mm 2g
Certifica-
tion body
Standard License
number
Approved as
VDE IEC 60934 400028127 Circuit Breaker for
Equipment
UL UL 1077 E140459 Supplementary
Protector
UL CSA 22.2
No.235
E140459 Supplementary
Protector
CSA CSA 22.2
No.235
250505 Supplementary
Protector

Products related to this Datasheet

CIR BRKR THRMMAG 5A 240VAC 28VDC
Available Quantity: 625
Unit Price: 31.64
CIR BRKR THRMMAG 2A 240VAC 28VDC
Available Quantity: 579
Unit Price: 31.64
CIR BRKR 10A 240VAC 28VDC
Available Quantity: 367
Unit Price: 31.64
CIR BRKR 15A 240VAC 28VDC
Available Quantity: 116
Unit Price: 31.64
CIR BRKR THRMMAG 4A 240VAC 28VDC
Available Quantity: 108
Unit Price: 31.64
CIR BRKR THRMMAG 1A 240VAC 28VDC
Available Quantity: 70
Unit Price: 31.64
CIR BRKR 12A 240VAC 28VDC
Available Quantity: 3
Unit Price: 31.64
CIR BRKR 16A 240VAC 28VDC
Available Quantity: 2
Unit Price: 31.64
CIR BRKR THRMMAG 8A 240VAC 28VDC
Available Quantity: 1
Unit Price: 31.64
CIR BRKR 500MA 240VAC 28VDC
Available Quantity: 0
Unit Price: 31.64
CIR BRKR THRMMAG 6A 240VAC 28VDC
Available Quantity: 0
Unit Price: 31.64